Dynair SVP Fire fighting lobbies

The SVP series are Pressurizing units for fire-fighting lobbies, available in multiple different setups. The unit consists of a control panel, a pressurization unit with DC or EC motors, auxiliary batteries, and remote sensors, depending on the chosen model. The pressurization system can be activated in emergency conditions either autonomously by the sensors, or manually from a fire protection control unit, via remote access.

CATALOGUE

Operation:

The pressurization system can be activated in emergency situations, either independently (by having the system connected to conventional smoke or heat detectors) or from an external signal coming from a fire protection control unit (via remote input).
The REI fire protection doors of the fire lobby are automatically closed by electronically releasing the locks. At the same time, the pressirizer puts the room under over pressure, reaching the minimum threshold of 30 Pa.
Once this pressure value is reached, the unit modulates its operation, to keep the pressure above 30 Pa.
The system works for a minimum of 120 minutes, even in the event of a blackout, thanks to the included batteries. When a door is opened, the system reduces its overpressure, allowing the door to close correctly. After a maximum of 2 seconds, the pressure inside the firefighting room returns to at least 30 Pa.

Installation:

Correct installation of an SVP unit requires a dedicated power line with an adequately sized magnetic circuit breaker, that fits the local laws and standards. An air duct system is also required, with EI120 certification, possibly from the REIDUCT series, with the least possible number of bends or restrictions. The pressurization unit must be placed on the wall, right below the ceiling, so people are not directly in the path of the airflow. The control panel must be placed at an accessible height in compliance with the latest laws and electrical standards, and can not be placed in areas with automatic extinguishing systems, ora areas exposed to weather. SVP systems must not be installed in rooms with potential fire load.

Available versions:

All SVP units require 230V~50Hz.

  • SVP1:

    • Max current: 2 A
    • Max flow rate: 2700 m3/h
    • Max overpressure: 270 Pa
    • Designed for emeregeny use only
  • SVP2:

    • Max current: 2.65 A
    • Max flow rate: 2200 m3/h
    • Max overpressure: 300 Pa
    • EC brushless motor
    • Suitable for 24h operation
  • SVP2+:

    • Max current: 1.7 A
    • Max flow rate: 3300 m3/h
    • Max overpressure: 400 Pa
    • EC brushless motor
    • Suitable for 24h operation
  • SVP4:

    • Max current: 3.9 A
    • Max flow rate: 4400 m3/h
    • Max overpressure: 650 Pa
    • EC brushless motor
    • Suitable for 24h operation
  • SVP5:

    • Max current: 3.9 A
    • Max flow rate: 6500 m3/h
    • Max overpressure: 400 Pa
    • EC brushless motor
    • Suitable for 24h operation

For a wide variety of accessories, see the catalogue.

For further details, feel free to contact KOMPEL Kft.